TX® (C) 331 150/250V 2P0.75
TX® (C) 331 150/250V 2P0.75
TX® (C) 331 150/250V 2P0.75
Mehr lesen- Nexans ref. : 10171345
- EAN : 3427650095465
Beschreibung
Beschreibung
Normen
-
Produkt448-010-3-10; IEC 60228
-
InstallationIEC 60092-350; IEC 60092-360; IEC 60092-376
-
TestsIEC 60331-1 or 2; IEC 60332-3-22; IEC 60754-1; IEC 60754-2; IEC 61034
Application
TX® (C) 331 150/250 V fire resistant overall screened twisted pair cables maintain circuit integrity in case of fire by meeting performances requirements from the IEC 60331 series for 90 minutes. These telecommunication and instrumentation cables provide a medium protection aganist external electromagnetic disturbances. Designed with halogen-free fire retardant materials, they provide optimum safety for people and maximal asset protection against all risks of fire.
Design
- Conductor:
Bare copper
Stranded class 2
- Insulation:
Mica tape + XLPE (cross-linked polyethylene)
Optional: Special fire resistant HF 90 (halogen-free compound)
with INFITTM technology - Collective screen:
Alu/polyester tape with a tinned copper drain wire
- Outer sheath:
Polyolefin SHF1 (SHF2 on request)
Colour: orange
Marking
I NEXANS I - TX (C) 331 150/250 V "n" x 2 or 3" x s" mm² 90 °C IEC 60092-376 IEC 60332-3-22 Cat. A IEC 60331-1/2 ww/yy - *CE* + metric marking
Core identification
Core 1: white
Core 2: blue
Core 3: red
Double identification: core and pair.
Eigenschaften
Eigenschaften
Konstruktionsmerkmale
Konstruktionsmerkmale
Abmessungsmerkmale
Abmessungsmerkmale
Elektrische Eigenschaften
Elektrische Eigenschaften
Anwendungsmerkmale
Anwendungsmerkmale
Ressourcen
Ressourcen
Unsere Websites
Wählen Sie Ihr Land aus, um unsere Produkte und Lösungen zu finden
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania